Fire Door Inspection in England: Requirements for Block Managers
For residential blocks in England whose top storey is more than 11 metres above ground level, responsible persons must check communal fire doors at least every three months and use best endeavours to check flat entrance fire doors at least every 12 months. This threshold concerns the top storey, not the roof height. Routine checks monitor condition, while the fire-risk assessment determines whether doors provide adequate protection. [2]

1. Establish which requirements apply
Regulation 10 covers blocks with two or more domestic premises and common parts used for evacuation, including purpose-built blocks and conversions. [2] The government’s September 2023 responsibilities guide also identifies residential parts of mixed-use buildings as within scope. [3]
- Required where the top storey is more than 11 metres above ground level: the prescribed checks cover communal fire doors and flat entrance fire doors, including their self-closing devices, at the intervals set out above. [2]
- Required regardless of height: general fire precautions and maintenance remain necessary. Where the top storey does not exceed the threshold, all fire doors, including flat entrance doors, must still provide adequate protection, although the specific checking intervals do not apply. [1]
- Required resident information: provide fire-door information as soon as reasonably practicable after residents move in, and remind all residents at intervals not exceeding 12 months starting from when the regulations came into force. Explain keeping doors closed, not tampering with doors or closers, and reporting faults or damage immediately. [2]
- Excluded: lift landing doors are outside the prescribed fire-door checks. [1]
- Optional recording format: checklists or electronic records can be used; the government guidance includes a sample checklist. [2]
The responsible person may be the freeholder, managing agent or another person controlling the premises. [2] Appointing a contractor to assist does not simply transfer that responsibility. [3]
2. Separate routine checks from assessment
Routine checks monitor visible condition and functionality; the fire-risk assessment determines whether a door’s resistance to fire and smoke is adequate for the building’s risk. [2] Article 9 requires a suitable and sufficient fire-risk assessment. If none exists, arrange one as soon as practicably possible. [2]
Routine checks assume the assessment has already considered door suitability. They do not establish inherent fire resistance or replace periodic specialist assessment, potentially including sampling during a fire-risk assessment. [2]
Appropriately instructed caretakers, housing officers, managing agents or maintenance staff can carry out the basic visual checks without a specialist. [2] Give them a clear boundary: record uncertainty and refer it for competent assessment rather than assigning an unsupported fire-resistance rating. [2]
3. Prepare the door list and access appointments
- Identify relevant doors. Use the fire-risk assessment to identify which doors need checking. [2] A door register listing locations and applicable intervals is a suggested management tool.
- Prepare staff instructions. Give the checker a checklist or electronic record covering closing action and visible condition. [2]
- Arrange access. Both sides of each flat entrance door need checking, so agree access with residents in advance. Offering several appointment times may help; except in very small blocks, checking every door in one visit may be impossible. [2]
Plan return visits alongside the initial appointments so unsuccessful access attempts remain part of the checking programme.
4. Test whether each door closes fully
A fitted closer is not enough: the door must close fully into its frame without assistance, except that doors to plant rooms, service cupboards and risers may instead be kept locked shut. [2] Use this sequence:
- Inspect the closer. Look for visible damage before testing its operation. [2]
- Release from fully open. Check whether the door closes completely into its frame, overcoming latch resistance or friction against the floor. [2]
- Repeat from approximately 15 degrees open. Confirm it again closes fully without help. [2]
- Check the final position. Confirm the door closes correctly around the whole frame, rather than merely appearing shut at the latch. [2]
- Check sequencing where applicable. If double-door leaves need to close in a particular order and a door selector is fitted, check its operation. [2]
For a useful action record, record the two closing-test results separately and describe any failure, such as catching on the floor or stopping at the latch. Identified repairs must be carried out by a competent contractor as soon as reasonably practicable. [2]
5. Check gaps, components and alterations
Alongside the closing test, examine visible condition and look for damage, alterations or replacement components. [2]
- Door and surroundings: inspect the leaf, frame, wall securing the frame, glazing and associated panels for visible damage or alteration. [2]
- Hinges and ironmongery: look for loose or missing hinge screws, defective fittings and closer damage. [2]
- Letterbox and openings: check the letterbox is firmly closed and not jammed open, and glazing apertures and grilles show no visible damage or alteration. [2]
- Frame gaps: government guidance states the industry-standard gap should never exceed 4 mm, except at the bottom; a gap-tester card may be used. The bottom gap should be as small as practicable without creating a snagging risk if the door drops on its hinges. [2]
- Fitted strips and seals: check intumescent strips and smoke seals are undamaged, contact the door edge or frame, and have not been painted over. Their original absence may be acceptable, subject to the fire-risk assessment. [2]
Flag doubtful replacement doors rather than guessing their performance from appearance. Where a replacement door’s fire-resisting status is uncertain, the resident must confirm it is fire-resisting and competently installed, and provide supporting technical information. [2] Record the concern for assessment: a visual check does not establish inherent fire resistance. [2]
6. Record failed access and follow up
Regulation 10 requires a record, over every 12-month period, of the steps taken to check flat entrance doors, including unsuccessful access. [2] An unanswered appointment should therefore remain visible in the programme rather than being marked as a completed check.
Use an access log with these suggested fields—not prescribed statutory wording:
- Flat or door reference.
- Proposed appointment date and time.
- Contact method and outcome, distinguishing no answer from refusal.
- References to retained access requests and replies.
- Next action, responsible staff member and follow-up date.
The following is a practical follow-up sequence, not a fixed legal procedure:
- Save the failed-attempt record and correspondence seeking permission; retained correspondence can demonstrate efforts to obtain access. [1]
- Contact the resident again and offer alternative appointments, explaining why both sides of the door need checking. [2]
- Assign the next action and keep the case open until access is achieved or an escalation decision is recorded.
For persistent refusal or an impasse, consider legal advice about obtaining access. The government’s responsibilities guide notes that a court order may be obtained after an impasse. [3]
7. Turn findings into an action record
Give each finding an owner and a next step. Beyond the required record of steps taken to check flat entrance doors, the following fields are a recommended defect-management workflow, not an officially prescribed form. [2]
- Identification: door reference and location, check date and checker.
- Results: access status, both closing-test results and visible findings.
- Evidence: references to photographs, correspondence and technical information.
- Action: next step, named owner and risk-based target date.
- Verification: completion date, person verifying, repeat-check results and outstanding assessment.
Example: closing failure
Illustrative entry: access obtained; door closes from fully open but stops short during the approximately 15-degree test. Refer to a competent contractor to investigate and repair. Assign the maintenance lead to arrange the work, record the repair and repeat both closing tests before closing the action. Identified repairs require a competent contractor and must be completed as soon as reasonably practicable. [2]
Example: doubtful replacement
Illustrative entry: replacement door’s fire-resisting status unclear. Request technical and installation information from the resident, then obtain competent assessment. [2] Assign the building manager to track the documents, retain the assessment outcome and record any resulting work separately.
Set follow-up according to risk: obvious defects should be rectified as soon as reasonably practicable, not left until the next scheduled inspection. [2][3]
8. Decide between repair, assessment and replacement
Missing modern features alone do not condemn an older door. Absence of certification, the original absence of intumescent strips or smoke seals, or failure to meet current new-build standards does not by itself require replacement. Condition, gaps, closing performance and adequacy for the assessed fire risk matter. [2]
Equally, age is not proof of acceptability: the fire-risk assessment may identify a weakness requiring upgrading or replacement. [3] Use these decision routes:
- Functional or condition defect: arrange competent remedial attention. Damage, excessive gaps or a faulty closer may warrant more detailed assessment before deciding the remedy. [1][2]
- Uncertain fire performance or suitability: obtain competent assessment through the fire-risk assessment process rather than asking the routine checker to establish inherent fire resistance. [2]
- Established inadequacy: where the fire-risk assessment determines replacement is needed, a competent person must undertake it. [2]
For close-out, record the competent decision and reasons, completed work and verification outcome. Keep the door in the applicable checking programme and continue tracking unresolved actions.
References
- Fact sheet: Fire doors (regulation 10) – GOV.UK (gov.uk, 2023)
- Fire Safety (England) Regulations 2022: fire door guidance (accessible) – GOV.UK (gov.uk, 2022)
- Check your fire safety responsibilities under the Fire Safety (England) (service.gov.uk, 2023)